發布日(ri)期:2017-12-13 閱讀次(ci)數:795
1、機械性(xing)(xing)能(neng)(neng)(neng)主要考慮其承載(zai)性(xing)(xing)能(neng)(neng)(neng)、耐磨(mo)性(xing)(xing)。把整塊(kuai)全鋼(gang)(gang)防靜電(dian)(dian)活(huo)動(dong)地板(ban)裝置在橫梁支架上(shang),調(diao)平(ping)全鋼(gang)(gang)防靜電(dian)(dian)活(huo)動(dong)地板(ban)后,其承載(zai)才(cai)能(neng)(neng)(neng)應(ying)到達(da)平(ping)均載(zai)荷大于12500N/m2,全鋼(gang)(gang)防靜電(dian)(dian)活(huo)動(dong)地板(ban)上(shang)任何部位的集中荷載(zai)應(ying)大于300kg,撓度(du)小于2mm,并無永世(shi)性(xing)(xing)變形(xing)。可調(diao)支撐應(ying)能(neng)(neng)(neng)接(jie)受1000kg以上(shang)的垂(chui)直(zhi)負荷,且板(ban)面應(ying)有一定的耐磨(mo)性(xing)(xing),色牢度(du)達(da)7級以上(shang)。
2、防靜(jing)(jing)(jing)電(dian)性能(neng)主要是系統電(dian)阻、外表電(dian)阻。這就在于全鋼(gang)(gang)防靜(jing)(jing)(jing)電(dian)活(huo)(huo)(huo)動地(di)(di)板貼面面層必(bi)需保(bao)證能(neng)盡快地(di)(di)導走靜(jing)(jing)(jing)電(dian)。SJT10796-2001《全鋼(gang)(gang)防靜(jing)(jing)(jing)電(dian)活(huo)(huo)(huo)動地(di)(di)板通用(yong)標準》規則:全鋼(gang)(gang)防靜(jing)(jing)(jing)電(dian)活(huo)(huo)(huo)動地(di)(di)板系統電(dian)阻應為1.0×106Ω~1.0×108Ω。
全(quan)鋼防(fang)靜電活(huo)動地(di)板除應(ying)滿足上(shang)述機(ji)械性(xing)能要(yao)求和電性(xing)能要(yao)求之外,還應(ying)具有下列特性(xing):
1、地板的(de)(de)外表面應進行(xing)可靠的(de)(de)貼封,以防止受潮和吸(xi)塵。
2、地板(ban)在受潮、熱、冷(leng)等環(huan)境因素影響時(shi),其外形(xing)尺寸的伸縮量(liang)應小于1mm,板(ban)面的撓曲變形(xing)量(liang)應小于0.5mm。
3、全鋼防(fang)靜電活(huo)動地(di)板(ban)應具(ju)有耐(nai)油(you)、耐(nai)腐蝕的性能(neng)。
4、全鋼防靜電活動地板表(biao)面(mian)應高耐磨、不(bu)打滑(hua)、不(bu)開裂、不(bu)開膠、不(bu)起塵、不(bu)吸塵、易清掃。